Sign In | Join Free | My chinacsw.com
China YUEQING HEYI ELECTRICAL CO,LTD logo
YUEQING HEYI ELECTRICAL CO,LTD
HEYI's vision is leading global split core CT manufacture and energy solution provider.
Active Member

5 Years

Home > Hall Current Sensor >

D-K182T Open Loop Mode Dismountable Hall Effect Current Sensor for DC, AC or pulsed currents measurement

YUEQING HEYI ELECTRICAL CO,LTD
Contact Now

D-K182T Open Loop Mode Dismountable Hall Effect Current Sensor for DC, AC or pulsed currents measurement

  • 1
  • 2

Brand Name : HEYI

Model Number : D-K182T

Place of Origin : China

MOQ : 1 pcs

Price : USD 195/pcs

Payment Terms : L/C, T/T, Western Union

Supply Ability : 50000pcs per year

Delivery Time : 5-8 work days

Packaging Details : box

Rated current(Ipn) : 2000/3000/4000/5000/6000A

Rated output : 20mA

Supply voltage : 24V

Galvanic isolation : @ 50HZ,AC,1min, 6KV

Storage temperature : -40 to +125 ℃

Contact Now

D-K182T Series Open Loop Mode Dismountable Hall Effect Current Sensor

D-K182T series dis mountable hall effect current sensor is an open loop device based on the measuring principle of the hall effect, with a galvanic isolation between primary and secondary circuit. It provides accurate electronic measurement of DC, AC or pulsed currents.

D-K182T Open Loop Mode Dismountable Hall Effect Current Sensor for DC, AC or pulsed currents measurement

Type

D-K182T-

2000A

D-K182T-

3000A

D-K182T-

4000A

D-K182T-

5000A

D-K182T-

6000A

Unit
Rated current(Ipn) 2000 3000 4000 5000 6000 A
Measure range(Ip) 0—2400 0—3600 0—4800 0—6000 0—7200 A
Rated output @Ip=±Ipn 20 mA
Supply voltage +24 V
Power Consumption <25 mA
Offset voltage @Ip=0 ±20 mV
Magnetic offset @Ip=±Ipn-0 ±30 mV
Offset drift @ -40~+85℃ ≤±0.5 mV/℃
Output drift @ -40~+85℃ ≤±0.5 mV/℃
Linearity @Ip=0-±Ipn ≤1 %FS

Response time

@50A/μS, 10%-90% ≤10 μs
Galvanic isolation @ 50HZ,AC,1min 6 KV

Applications

  • Variable speed drives
  • Welding machine
  • Battery supplied applications
  • UPS
  • Uninterruptible Power Supplies (UPS)
  • Electrochemical

Mechanical dimension(for reference only)

D-K182T Open Loop Mode Dismountable Hall Effect Current Sensor for DC, AC or pulsed currents measurement

Remarks:

1. All dimensions are in mm.

2. General tolerance ±1mm.

3. Elucidation: 1:+24V 2:GND 3:I0UT 4:GND


Quality D-K182T Open Loop Mode Dismountable Hall Effect Current Sensor for DC, AC or pulsed currents measurement for sale

D-K182T Open Loop Mode Dismountable Hall Effect Current Sensor for DC, AC or pulsed currents measurement Images

Inquiry Cart 0
Send your message to this supplier
 
*From:
*To: YUEQING HEYI ELECTRICAL CO,LTD
*Subject:
*Message:
Characters Remaining: (0/3000)
 
Inquiry Cart 0